UPS 200 KVA / 200 KW
- Capacity : 200 KVA / 200 KW
- Power Factor : 0.99
- Input Voltage : 400 Vac 3-phase with neutral (rectifier); 380/400/415 Vac 3-phase with neutral (bypass
- Output Voltage : 380/400/415 Vac 3-phase with neutral
- Tower
- Unit Utama
Product Description
Rating (kVA) | 30 | 40 | 60 | 80 | 100 | 125 | 160 |
Nominal power (kW) | 30 | 40 | 60 | 80 | 100 | 125 | 160 |
UPS dimensions WxDxH (mm) | 460x650x1230 | 560x940x1505 | 560x940x1800 | ||||
UPS weight (kg) | 120 | 140 | 210 | 225 | 320 | 360 | 380 |
UPS weight with int. battery (kg) |
365 | 385 | 770 | 785 | – | – | – |
Battery configuration | Internal or external, 360 to 372 cells, VRLA (other options) | External 360 to 372 cells, VRLA (other options) | |||||
Max autonomy with int. battery 70% load (min) |
11 | 7 | 12 | 8 | – | – | – |
Input
Connection type | Hardwired 4w | Hardwired 4w (rectifier), 4w (bypass) |
Nominal voltage | 400 Vac 3-phase with neutral (rectifier) 380/400/415 Vac 3-phase with neutral (bypass) |
|
Voltage tolerance | -20%, +15% (rectifier); ±10% (bypass) | |
Frequency and range | 50/60 Hz, 45 to 65 Hz | |
Power factor | >0.99 | |
Current distortion (THDi) | <3% |
Output
Connection type | Hardwired 4w |
Nominal voltage | 380/400/415 Vac 3-phase with neutral |
Frequency | 50/60 Hz |
Voltage regulation | Static: ±1%; dynamic: IEC/EN 62040-3 Class 1 |
Power factor | Up to 1, without power derating |
Overload capacity* | Inverter: 110% for 10 min, 125% for 5 min, 150% for 30 s, >150% for 0.1 s; bypass: 150% continuous, 1000% for 1 cycle |
Efficiency (AC/AC)** | Up to 99% |
Classification as per IEC EN 62040-3 | VFI-SS-111 |
*conditions apply **according to IEC/EN 62040-3
Connectivity and function extensions
Front panel | Graphic display, mimic LED panel and keyboard, local EPO |
Remote communication | Included (30 to 160 kVA): backfeed protection monitoring contact. Included (60 to 160 kVA): serial RS232 and USB; input terminal block (remote emergency power off, battery circuit breaker aux. cont. external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.). Optional: SNMP adapter (Ethernet), Web interface (Ethernet), ModBus-TCP/IP (Ethernet), ModBus-RTU (RS485), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software |
Optional function extensions | Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit, load-sync for single UPS and load-sync box (2 UPS systems); other options on request |
System
Protection degree | IP 20 | ||||||
Colour | RAL 9005 | ||||||
Installation layout | 10 cm wall-gap, side by side installation allowed | Wall and side by side installation allowed, 80 cm clearance on one side with internal battery | |||||
Accessibility | Front and top access, bottom cable entry | Front and top access, side access (with internal battery) bottom cable entry | Front access, side access (with internal battery), bottom cable entry |
Environmental
UPS operating temperature | 0°C to +40°C |
UPS storage temperature | -10°C to +70°C |
Altitude (AMSL) | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
Audible noise at 1 m (dBA) | <60 |
Standards and certifications
Quality assurance, environment, health and safety |
ISO 9001:2015, ISO 14001:2015, BS OHSAS 18001:2007 |
Safety | IEC/EN 62040-1 |
EMC | IEC/EN 62040-2 |
Environmental aspects | IEC/EN 62040-4 |
Test and performance | IEC/EN 62040-3 |
Protection degree | IEC 60529 |
Marking | CE |